Синхрон С ООД

Fire Protection and Security

Synchron S logo 30years en

 

Phone: + 359 2 944 14 04

Mobile: + 359 884 852 708

E-mail: synchron-s@synchron-s.com

Gas extinguishing systems

A key feature of the modern gas fire extinguishing systems are their extremely effectiveness. They extinguish fire in its early stages in the critical seconds before its expansion. The low value of the parameter discharge time and the high value of the parameter duration of protection ensure full control and fast extinguishing of the fire without the possibility of re-ignition.

Efficiency of gas extinguishing systems is largely due to the mechanism of fire extinguishing. Ii depends on extinguishing agent and goes through several stages - the removal of combustion heat, reduction of oxygen level in the room and breaking the self-sustaining chain reaction of the combustion process. 

Depending on the specific application, fire risk and the type of room, gas extinguishing systems which we design and install are based on the inert gases argon or nitrogen or chemical gases FM-200 and Novec 1230 (FK-5-1-12).


Key features of the gas fire extinguishing systems

  • Suitable for the protection of people, property and equipment in enclosed spaces
  • Suitable for hazardous areas where localization and suppression of fire should be fast, clean and safe
  • Protecting the environment , equipment and safe for humans
  • Electrically non-conductive, non-corrosive and this makes them suitable for fire protection of areas with active electrical and electronic equipment
  • Not causing thermal shock to protect equipment
  • Suitable for rooms with high ceilings and low temperatures
  • Ability to reach hidden fires
  • Suitable fire, wherein the fire is not set or has multiple sources
  • Do not leave any particles or residues after release of the agent and does not require the process of cleaning up after fire
  • Visibility is not reduced during discharge of the agent
  • Efficient over a wide range of fires: Class A, B and fires in rooms with active electrical and electronic equipment
  • Typical applications include data centres, rooms with electrical and electronic equipment, telecommunication equipment, libraries, archives, museums and galleries, premises with production processes, warehouses with flammable liquids, transformer rooms and more.

Data Center

Key requirement for modern gas fire extinguishing agent is their safety for people and the environment. Our gas extinguishing systems have high levels of personal safety. They stop the burning process at high oxygen concentration at which there is no risk to people. Particularly effective are extinguishing systems with Novec 1230 (FK-5-1-12). Novec 1230 (FK-5-1-12) is a new chemical fire extinguishing agent. It has zero potential for ozone layer depletion, short atmospheric lifetime of 3 to 5 days and a global warming potential 1, which meets the latest requirements for clean and safe extinguishing agent. Its low toxicity, combined with the low design concentration provides the widest range of safety compared with other gaseous agents based on hydrocarbons, carbon dioxide or inert gases.

Matrix Design


Innovative i FLOW technology for fire suppression with an inert gas

 Disadvantages of the gas fire extinguishing systems is the creation of a very high pressure and turbulence during the discharge of the extinguishing agent in the room, which can cause damage to the equipment. i FLOW technology eliminates this risk. The main advantages of the new technology are:

  • Eliminates the pressure peak immediately after discharge of the agent - 2,7 times lower peak
  • Provides maximum outlet pressure of 60/40 bar at a cylinder pressure of 300/200 bar
  • Provides constant flow of extinguishing agent throughout its release without overpressure and turbulence
  • Eliminates the need of having a more venting area and exhaust dampers in the room
  • Innovative method for matrix design of the cylinders in rows and columns saves resources - lower cost of installation and maintenance, less installation space


Quality and reliability of installed systems

The systems installed by our company meet the requirements of standards NFPA 2001 (2008), EN 15004 and comply with all applicable local regulations. The equipment is manufactured by the leading global companies and is certified by internationally recognized organizations VdS, LPCB, CNPP, UNIIPO, UL and others. The installations are performed by trained professionals. Our company is certified for maintenance and servicing of fire protection systems issued by the Ministry of Interior.